BB101:2018 builds on CIBSE TM52:2013 by defining comfort plus air quality checks for both free running and mechanical ventilated / cooled teaching and learning spaces. These are:
For free running teaching and learning spaces:
· Adaptive comfort analysis.
o Typical use of TM52 category II.
o TM52:2013 criteria 1, 2 & 3 assessment.
· Air quality assessment:
o Daily occupied average CO2 1500PPM.
o Max 20 mins occupied CO2 2000PPM.
o Design for 1200PPM majority of the time (new build).
o Design for 1750PPM majority of the time (refurb).
The max 20 mins test requires Apachesim to be set with a 10-minute simulation timestep.