×
Menu
Index

2 Model Preparation

Models should be preparing in accordance with BB101:2018; in summary:
 
·         Set the CIBSE DSY1 2020 (50th. percentile range) weather file most appropriate to the location of the school building.
·         Set space conditions (casual gains, occupancy etc). as BB101:2018 section 8.1 & 8.5.2.
·         Set external ambient CO2 concentration of 400ppm.
·         Openings should be defined correctly in Macroflo to reasonably represent the design as BB101:2018 section 8.3.