Table 21 Inside Surface Resistance (Table A3.5 CIBSE Guide)
|
|
|
Surface resistance (m²K/W)
|
|
|
Building element
|
Heat flow
|
High emissivity
|
Low emissivity
|
|
|
|
factor
|
factor
|
|
Walls
|
Horizontal
|
0.12
|
0.3
|
|
|
|
|
|
|
Ceilings or roofs,
|
Upward
|
0.1
|
0.22
|
|
flat or pitched
|
|
|
|
|
floors
|
|
|
|
|
|
|
|
|
|
Ceilings and floors
|
Downward
|
0.14
|
0.55
|
Notes:
1. High emissivity factor assumes ε 1 = ε 2 = 0.90 (most building materials),
Low emissivity factor assumes ε 1 = 0.90, ε 2 = 0.05,
2. Surface temperatures are 20°C
3. Air speed at the surface is assumed to be less than or equal to 0.1 m/s