Data common to Part L1 and Part L2
 
 
Building 
This tab deals with Part L data at the building level (as distinct from data describing individual rooms or constructions).
Building Type
Part L distinguishes between various building types. The choices are:
Dwelling – requires analysis by Part L1
Dwelling extension – a category within Part L1 (not currently supported)
Residential building – a category within Part L2 (ADL2 Table 2)
Office – a category within Part L2 (ADL2 Table 2, paragraph 1.62 (CPR Method) & paragraph 1.70 - Whole-building Method)
Place of assembly or shop – a category within Part L2 (ADL2 Table 2).
Industrial or storage building – a category within Part L2 (ADL2 Table 2)
School – a category within Part L2 (ADL2 paragraph 1.72 - Whole-building Method)
Hospital – a category within Part L2 (ADL2 paragraph 1.72 - Whole-building Method)
Other – not eligible for Part L2 Whole-building Method (ADL2 paragraph 1.70)
New or existing
Indicate whether the building is new or existing. An existing building may have a less stringent CPR target for air-conditioning and mechanical ventilation in the L2 Elemental Method. Where alterations are made to the fabric of existing buildings, existing elements that are not subject to alteration may not need to comply with the standards of the current regulations. However, the software currently applies the same checks to all elements.
Data for Part L1 
Heating System 
This tab contains data describing the dwelling’s heating system. This data is used by all three L1 methods, with the exception of data fields appearing in green, which are used only by the Carbon Index (SAP) Method. All other Part L1 tabs are used exclusively by the Carbon Index Method.
This tab provides access to the Boiler Efficiency Database maintained by DEFRA. This database is updated on the first day of each month and the latest version may be downloaded from 
www.boilers.org.uk. The database file, ‘bedf.dat’, should be placed in the folder ‘IES\apps\Regs’.
 
Heating system (L1 Elemental Method and SAP Table 4a)
The type of system providing space-heating in the dwelling. The options (underlined) are the system types appearing in SAP[8] Table 4a. Depending on the heating system selected, further data fields are presented, as shown below beneath each option:
CENTRAL HEATING SYSTEM WITH RADIATORS OR UNDERFLOOR HEATING 
Heating system type 
Select a central heating system type:
Gas or oil boiler 
Click on a radio button to indicate the source of the boiler efficiency data:
Use SAP Table 4b 
– to take efficiency and other data from this table
Boiler type (2 fields) – select options to describe the gas/oil boiler for SAP Table 4b 
Boiler type (2 fields) – select options to describe the gas/oil boiler for SAP Table 4b 
Enter manufacturer’s efficiency? – tick this box to override the SAP Table 4b efficiency 
Select from boiler database 
– to take efficiency and other data from the boiler database
Select from database – accesses the boiler database allowing you to select a boiler 
Detail – displays the detailed parameters for the selected boiler 
Efficiency adjustments (SAP Table 4c) due to... 
These options are used to calculate the Adjusted Efficiency (SAP Table 4c). 
Low temperature distribution system – select an option for SAP Table 4c 
Control system – select an option for SAP Table 4c 
Heat emitter (SAP Table 4d) – select a type of heat emitter for SAP Table 4d 
Solid fuel boiler 
Solid fuel boiler type – select an option to describe the boiler for SAP Table 4a 
Electric Boiler 
Electric boiler type – select an option to describe the boiler for SAP Table 4a 
Electric CPSU data (SAP Appendix F) – specify CPSU parameters where applicable for use in SAP Appendix F: 
CPSU cylinder size (litres) 
CPSU operating temperature (winter) 
Heat Pumps 
Heat pump type 
– select an option to describe the heat pump for SAP Table 4a
COMMUNITY HEATING SCHEME 
Heating scheme type 
Select a community heating scheme type (determines the method used for the Carbon Index calculation):
CHP (includes instances where some heat is supplied from community boilers). 
Recovered heat from power station (includes instances where some heat is supplied from community boilers) – treated differently from CHP in Carbon Index calculation. 
Community boilers  (without any CHP or recovered heat component) – treated with a dedicated section of the SAP worksheet. With this option the parameter ‘Fraction of heat from CHP or fraction of heat recovered from power station’ on the SAP 9* & 10* Space-heating (community heating) tab should be set to 0. 
STORAGE RADIATOR SYSTEM 
Tariff – select Off-peak or 24-hour tariff for SAP Table 4a 
Heater type – select a type of storage heater for SAP Table 4a 
WARM-AIR SYSTEM 
Air heating System - select a type of warm-air system for SAP Table 4a
Heater Type - Select a heater type for SAP Table 4a - add 40m3/s for each flueless gar fire if present
 
Data common to Part L1 and Part L2
 
SAP 4 & 10. Water heating 
The boxes on this tab relate to those in Section 4 (Water-heating energy requirements, boxes 39-52), and Section 10 (Fuel costs, boxes, 88-100 and 89*-100*) of the SAP worksheet. For guidance, see Sections 4 and 10 of SAP 2001.
Water heating system (SAP Table 4a)
Indicate the system used to provide hot water. The options (with the exception of the first) are those appearing in SAP Table 4a under ‘HOT-WATER-ONLY HEATING SYSTEMS’, with ‘Independent electric water heating system’ expanded into ‘Immersion heater (single)’ and ‘Immersion heater (dual)’ to provide the input data required for SAP Table 13 or (in the case of heat pumps) SAP Appendix G:
Provided by space heating system (but not heat pumps) 
Select this option if hot water is supplied by the space heating system, except in the case where space heating is provided by heat pumps.
Immersion heater (single) 
Select this option or the following if space heating is provided by heat pumps.
Immersion heater (dual) 
From a heat exchanger built into a gas warm-air system 
Single-point gas water heater 
Multi-point gas water heater 
Water heating fuel
Select a fuel or electricity tariff to be used in SAP Table 12 or, in the case of heat pumps, SAP Appendix G. The fuel must be consistent with the water heating system.
Is water heated by community heating?
This option is set automatically. If the heating system is set to COMMUNITY HEATING SCHEME and Water heating system (SAP Table 4a) is set to ‘Provided by space heating system (but not heat pumps)’, the box is ticked, with consequences for the calculations done in Section 4 of the SAP form.
Is there a hot water tank or other storage device?
If so, the following data must be entered to provide the data for boxes 41-42 of the SAP form:
Hot water storage volume (litres) 
Hot water storage type (SAP Table 2) – 
Data required for SAP Table 2 and it's footnotes
Is there a cylinder thermostat (SAP Table 2)? 
Insulation thickness (mm) (SAP Table 2) 
Area of solar panel (0 if none) (m2)
 
Enter the area of any solar panel used for water heating
Primary circuit and keep-hot losses (SAP Tables 3 & 4f)
Water heating system type 
Pick an appropriate category for SAP Table 3. If space heating is provided by heat pumps, the appropriate setting is ‘Electric immersion heater’.
 
Combi boiler? 
For a combination boiler, enter the following data used in the section of SAP Table 3 labelled ‘Additional losses for combi boilers’, an in the section of SAP Table 4f labelled ‘Electricity for maintaining keep-hot facility of a gas combi boiler’:
Keep-hot facility type 
Controlled by time clock? 
Electric power rating (W) (0 if unknown) 
  
SAP 5. Internal gains 
The boxes on this tab relate to box 53a of Section 5 of the SAP worksheet: Additional gains from Table 5. For guidance, see Section 5 of SAP 2001.
Central heating pump?
– Tick if there is a central heating pump (does not apply to community heating)
Warm-air heating system fans?
– Tick if there are warm-air heating system fans (does not apply to community heating)
Mechanical ventilation system
– Tick if there is a mechanical ventilation system (do not include if either of the two preceding boxes is ticked)
Oil pump, inside dwelling
– Tick if there is an oil pump inside the dwelling and therefore contributing to heat gains
 
SAP 9 & 10. Space-heating 
The boxes on this tab relate to Section 9 (Space-heating requirement, SAP boxes 81-87) and Section 10 (Fuel costs, SAP boxes 88-100) of the SAP worksheet, which apply if space and water heating is not provided by community heating. For guidance, see Sections 9 and 10 of SAP 2001.
Heat from secondary system (Table 11 & Appendix F)
The following provide the data for SAP Table 11 (Fraction of heat supplied by secondary heating system), SAP Table 4a (secondary system efficiency for SAP box 84) and the calculation of fuel costs in Section 10 of the SAP form. In the case of electric CPSUs, SAP Appendix F is used in place of Table 11.
Main system 
– This field, which is used as input to SAP Table 11 (for SAP box 82) is set automatically from data entered on the Heating System tab, as follows:
When Heating system is ‘CENTRAL HEATING...’ or ‘WARM-AIR SYSTEM’, ‘Main system’ is set to ‘Boiler’, except where ‘Heating system type’ is ‘Heat pumps’, when the setting is ‘Heat pump’. 
When Heating system is ‘STORAGE RADIATOR SYSTEM’, ‘Main system’ is set to ‘Fan assisted storage heaters’ or ‘Electric storage heaters not fan assisted’, depending on the Heater type. 
When Heating system is ‘ROOM HEATER SYSTEM’, the ‘Main system’ setting depends on ‘Room heater system type’ and ‘Heater type’. When ‘Room heater system type’ is ‘Gas’, the setting is ‘Gas room heaters’. When ‘Room heater system type’ is ‘Solid Fuel’, and ‘Heater type’ is any of the options beginning ‘Open fire...’, the setting is ‘Coal fires or other electric systems’. In all other cases the setting is ‘Coal or electric room heater’. 
When Heating system is ‘OTHER SPACE-HEATING SYSTEMS’ (which means Electric ceiling heating) ‘Main system’ is set to ‘Coal fires or other electric systems’ 
 
Secondary system 
– select options from the two boxes describing any secondary heating system for SAP Table 11 and Table 4a (ROOM HEATER SYSTEMS)
Additional gains (SAP Table 4f)
Describe additional gains from SAP Table 4f for inclusion in SAP boxes 87a-87e:
Central heating pumps? 
–  tick if there is a central heating water pump, or a CPSU pump (see SAP Appendix F) or a heat pump (see SAP Appendix G)
Boiler oil pump? – 
  tick in the case of an oil boiler to allow for the oil pump and flue fan
Gas boiler with flue fans? 
–  tick in the case of a gas boiler with a fan-assisted flue
 
SAP 9* & 10*. Space-heating (community heating) 
The boxes on this tab relate to ‘Section 9*’ (Space-heating requirement, SAP boxes 82*-88*), Section 10(*) (Fuel costs, SAP boxes 88-100) of the SAP worksheet, which apply if space and water heating is provided by community heating. For guidance, see Sections 9 and 10 of SAP 2001.
Fuel data from this tab is also used in the sections of the SAP form headed ‘Carbon Index (CI) for individual and community heating without CHP’ and ‘Carbon Index (CI) for community heating schemes with CHP or heat recovered from power stations’.
Community heating schemes use heat from one or more of the following three sources: CHP, recovered heat from power stations, and community boilers.
Fraction of heat from CHP unit or fraction of heat recovered from power station –
 for SAP box 83*. The remaining fraction is assumed to be provided by community boilers.
Distribution loss factor for group and community schemes (SAP Table 12a)
– select an option for the specification of distribution loss factor in SAP box 85*
Community boilers fuel (SAP Table 15) –
 identify the fuel used by community boilers (if present). In the case of community boilers supplementing CHP or heat recovered from power stations, this will be used to set carbon emission factors in the boxes to the left of SAP boxes 109* and 112*.  In the case of community heating without CHP or heat recovered from power stations, this setting is not used
 
The following fields apply only to community heating schemes using CHP:
Electrical efficiency of CHP unit (eg 0.3) – for SAP box 101*
Heat efficiency of CHP unit (eg 0.5) – for SAP box 102*
CHP fuel (SAP Table 15) – for SAP box 103*. Select a fuel for use in SAP Table 15: Carbon dioxide emission
CHP heat to power ratio (enter 0 if unknown) – for SAP box 106*