To access the TM52 Adaptive Comfort dialog, the user will enter VistaPro, then click on the Comfort settings toolbar button .
 
The Comfort settings dialog will appear where the user should then tick on the TM52 Adaptive Comfort tick box.
Figure 1 – Comfort Parameters Dialog
This will then allow the user to input the relevant information for the assessment.
Figure 2 – TM52 Adaptive Comfort Settings
 
 
 
Summer (elevated) air speed (m/s)
This air speed is used to calculate the operative temperature of each space in the assessment. The operative temperature is calculated using the formula:
 
Equation 1 – Operative Temperature
Where:
 (°C)
 (°C)
Building Category
The building category is used in calculating the maximum acceptable temperature ( .
 
Equation 2 – Maximum Acceptable Temperature
 
Where:
 exponentially weighted running mean of the daily mean outdoor air temperature
 
Category
Explanation
Suggested acceptable range (K)
Category I
High level of expectation only used for spaces occupied by very sensitive and fragile persons
2
Category II
Normal expectation (for new buildings and renovations)
3
Category III
A moderate expectation (used for existing buildings)
4
Table 1 – Building Categories
The CIBSE suggestion is that designers should aim to remain within the Category II limits. For TM52, Category II should be used. This will mean that:
 
Equation 3 – Maximum acceptable temperature Category II TM52