Shut-off and Setback Controls NECB 2020
This action reminds the user to integrate shut-off and setback controls to the schedules copied from the proposed model for use in the reference model (as B 5.2.8.3 & 5.2.11).
Temperature Control in Guest Rooms and Suites in Commercial
Temporary Lodgings
- The space temperature in each guest room and suite in a commercial temporary lodging shall be controlled so that it is automatically adjusted to a set-back temperature within 15 min of the space being unoccupied. (See Note A-5.2.8.3.(1).)
Shut-off and Setback ControlsOff-hours Controls
- Except as provided in Sentence (3), systems serving dwelling units or other areas that are not intended to operate continuously and whose zone-heating or -cooling capacity requirement is 5 kW or more shall be equipped with automatic controls capable of setting back or shutting down the systems during periods of non-use of the zones served. (See Note A-5.2.11.1.(1).)
- Controls required by Sentence (1) shall be capable of a) shutting down fan systems and/or heating and cooling equipment and auxiliaries, where appropriate, when conditioning is not required by the space,
- setting back the space-heating temperature setpoint,
- setting up the space-cooling temperature setpoint if the cooling system is required to operate during periods when the space is not in use,
- reducing or shutting off outdoor air intake during heating or cooling system operation when the space is not in use (see Note A-5.2.11.1.(2)(d)), and
- in the case of heat pumps, temporarily suppressing electrical back-up or adaptive anticipation of the recovery point in order to prevent the unit from resorting to supplementary heat at the time of recovery (see Notes A-5.2.ll.1.(2)(e) and A-5.2.8.5.(1)).
- Zones with a total heating or cooling capacity requirement of less than 5 kW may be controlled by readily accessible manual controls.
- Controls required by Sentence (1) shall be designed so that lowering a heating thermostat setpoint will not cause energy for cooling to be expended to reach the lowered setting and raising a cooling thermostat setpoint will not cause energy for heating to be expended to reach the raised setting.