Performance requirements

For buildings other than schools it is likely CIBSE TM52:2013, ISO 7730: 2005 or ASHRAE 55: 2013 will be utilised to assess comfort performance.
 
For schools in the UK & Eire BB101:2018 is the definitive guidance on performance. The performance standards in BB101:2018 require:
For buildings operating in a free running mode adaptive comfort is specified using CIBSE TM 52 (BB101:2018 7.6). This involves three criteria, taken together, to be used to assess the risk of overheating of the building in the UK, using the geographically closest CIBSE Design Summer Year (DSY1 2020 50th percentile) weather file. A room or building that fails any two of the three criteria is classed as overheating:
 
 
For buildings operating in a mechanically cooled mode PMV is specified as CIBSE Guide A (BB101:2018 3). This references ISO 7730 and PMV thresholds of:
 
With regards to internal air quality, BB101:2018 (2.4) criteria specifies that for natural ventilation or hybrid systems operating in natural mode:
For systems operating in mechanical ventilation or hybrid mechanical mode, BB101:2018 (2.4) criteria specifies that:
 
BB101:2018 1.2.3 and figure 1-2 describe system types and operating modes.
 
 
 
BB101:2018 figure 1-2
 
 
The VE provides tools for assessing performance requirements for all these standards via the VistaPro Comfort Analysis tool. Both natural and mechanical modes are assessable.