HTM Background

What is the Priority School Building Programme and design requirements?

The Priority School Building Programme (PSBP) is a centrally managed programme set up to address the needs of the schools most in need of urgent repair. Through the programme, 261 schools will be rebuilt or have their condition needs met by the Education Funding Agency (EFA). All schools within the programme will be delivered by the end of 2017. In May 2014, the Government announced a further phase of school development, known as PSBP2, which is a five-year programme operating between 2015 to 2021 and will undertake major rebuilding and refurbishment projects in schools and sixth form colleges in the very worst condition.
The Facility Output Specification forms the basis for the design of the PSBP Schools and has become the definitive guide to school design. The performance standards stipulated in PSBP requires three criteria, taken together, to be used to assess the risk of overheating of the building in the UK, using the geographically closest CIBSE Design Summer Year (DSY) weather file. A room or building that fails any two of the three criteria is classed as overheating:
With regards to internal air quality, TM52 criteria specifies that for natural ventilation or hybrid systems operating in natural mode:
For mechanical ventilation or hybrid systems operating in mechanical mode, TM52 criteria specifies that:
In addition to the mechanical and natural ventilation:
 

Why Choose Hybrid Thermal Mixing?

Ideal Environment:
Exceptionally Low Power Consumption:
 

HTM Key Features

Two versions of Monodraught’s HTM system are available, the HTM F and the HTM FS. Each system (or pair of HTM FS systems) is able to produce 360 l/s of daytime ventilation and 530 l/s of night-time cooling. A powder coated steel frame makes the system robust and easy to install This frame supports a body constructed from specialist acoustic panels which when combined with a low energy fan means that the systems maximum daytime operation sound level is under 35dB. The low leakage external damper is integrated within the system and has a high U-Value of 1.2Wm2K and when combined with the internal damper allows the system to supply tempered fresh air throughout the year. A combination of an intelligent controls system and sensors measuring the room, external and mixed air temperatures & CO2 levels allows the system to automatically control the internal environment. This control system can also be utilised for the operation of additional VENTSAIR facade systems and has a full data logging facility.
 
HTM F – Key Features
 
 
Full acoustic testing has been conducted at SRL (Sound Research Laboratories).
Sound reduction Index Measurements:

Ventilation Rate

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

300 l/s

  1. 4
  1. 6
  1. 4
  1. 5
  1. 7
  1. 0
  1. 7
  1. 7

Weighted Sound Reduction Index Rw (C:Ctr) = 31 dB
Tests were conducted with a standard 50 mm external louvre arrangement.
 
HTM FS - Key Features
Sound power levels of the HTM FS per unit at 32% fan speed:

Ventilation Rate

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

150 l/s

46

  1. 8
  1. 4
  1. 7
  1. 4
  1. 7
  1. 9
  1. 9

Typical Installation - Operation Detail

 
Cross Flow

Monodraught HTM system mounted at the rear of a room to assist with cross flow ventilation using openable windows on the facade. System automatically provides secure night time cooling through natural ventilation opening or fan assisted if required. Winter ventilation automatically modulates dampers to mix re-circulated air with external air to ensure optimum ventilation temperatures.
 
Single Sided Flow

Monodraught HTM system mounted on the facade (can be ducted to provide ventilation to the rear of deep plan rooms) to assist with single sided ventilation using openable windows. System automatically provides secure night time cooling through natural ventilation opening or fan assisted if required. Winter ventilation automatically modulates dampers to mix re-circulated air with external air to ensure optimum ventilation temperatures.
 
Additional Ventilation
Monodraught’s HTM is designed to work with and control a range of VENTSAIR Facade Ventilation System (VAF), as well as work in conjunction with other external openings such as windows.
The benefit of using VENTSAIR system is that they can be specified to suit different sized glazed frames or fitted with a flange to suit wall openings, as well provide controlled fresh air during the day and secure night time cooling. The HTM will automatically control the additional vents and the dampers can also be opened and closed manually via the systems control panel. These additional ventilation openings are often used in lieu of manual windows adding the benefit of secure night time cooling.
 
Control Strategy
The HTM incorporates a fully automatic control system based on a seasonal control strategy. The seasonal strategy is determined by time and date but is weather compensated to pick up unseasonal conditions. The system provides natural ventilation as the default method of ventilation indicating when manual windows or automatically opening dampers should be utilised to maximise IAQ and maintain comfort levels.
The control system incorporates a number of temperature sensors integral to the unit to monitor external temperature, mixed air temperature and supply air temperature. In addition, a wall mounted controller fitted with an internal temperature, CO2 sensor and user override are included as standard. Data is stored per minute on an integral data card for data analysis and compliance requirements.
 
Controls and user interface
Monodraught offer three wall controller options, each dependant on the room design and layout and the user’s requirements. One wall controller is required to be mounted within each room and will give the user certain functionality over the systems. Each controller houses temperature and CO2 sensors, with the exception of the Smart Screen Controller which requires a modular unit.
Openable Window: Allows the user to control the fan speed but will also indicate when they need to open windows to aid the system in providing ventilation.
Louvre Override: Allows the user to not only control the fan speed of the units but also regulate the amount that the VENTSAIR Facade system opens by if fitted.


HTM Case Study: Thomas Hickman School

On a winter day:

 

On a spring day:

Data

Max

Min

Average

 

Data

Max

Min

Average

Room Temperature

23 ° C

21 ° C

22 ° C

 

Room Temperature

24 ° C

21 ° C

23 ° C

External Temperature

7 ° C

0 ° C

5 ° C

 

External Temperature

17 ° C

6 ° C

13 ° C

Mixed Air Temperature

25 ° C

15 ° C

19 ° C

 

Mixed Air Temperature

24 ° C

13 ° C

20 ° C

CO2

1780 ppm

435 ppm

1300 ppm

 

CO2

1580 ppm

505 ppm

1145 ppm

Results between 8:30 – 15:30

 

Results between 8:30 – 15:30


 