Heat Transfer by Air Movement

ApacheSim models the following types of air movement:
 
The rate of heat transfer associated with a stream of air entering a space is
                                                                                          (22)
where
  is the air mass flow rate (kg/s),
  is the specific heat capacity of air at constant pressure (J/kg/K),
  is the supply temperature of the air (ºC ), and
  is the room mean air temperature of the air (ºC ).
Equation 22 embodies an assumption that the air displaced by the supply air is at the room mean air temperature, which is consistent with ApacheSim’s stirred tank model of the room air.
Air supply rates may be specified in various ways. A rate specified in terms of a volume flow in l/s is converted to a mass flow rate using a reference air density of 1.2 kg/m 3 . A rate specified in terms of l/s/m 2 is multiplied by room floor area and then converted as above. A rate specified in terms of air changes per hour is converted to a mass flow rate m using
                                                                                          (23)
where
 = 1.2 kg/m 3 is the reference air density,
  is the room volume (m 3 ) and
  is the air change rate (ach).
The water vapour gain associated with the air supply, which plays a part in the room’s latent balance, is
                                                                                                              (24)
where
  is the water vapour gain (kg/s)
  is the humidity ratio of the supply air (kg/kg)
  is the humidity ratio of the room air (kg/kg)
Carbon dioxide gain is treated in a similar way:
                                                                                                              (25)
where
  is the carbon dioxide gain (kg/s)
  is the carbon dioxide concentration of the supply air (kg/kg)
  is the carbon dioxide concentration of the room air (kg/kg)
 
In the case of an air supply for which the supply temperature is defined by an absolute profile, the supply humidity ratio is assumed to be that of the outside air, unless the supply air approaches saturation under this assumption. The supply air percentage saturation is limited by the greater of 90% and the outside air percentage saturation.
The carbon dioxide concentration of outside air is assumed to take the fixed value of 360 ppm (volumetric).
The calculation of air flow rates by MacroFlo and ApacheHVAC is dealt with in the sections devoted to these programs.