Appendix H: Modeling UFAD and DV in ApacheHVAC

The HVAC systems library includes two pre-defined UFAD system prototypes. One is intended for more humid climates for which dehumidification will be required, and thus includes an optional heat pipe/wheel/runaround coil in the AHU. The other simply excludes this feature. The labeled image of the prototype UFAD system below is as it appears in version 6.5 (VE 2012).
 
As a default until better data can be obtained, and assuming the occupant gain is placed 100% in the occupied zone, an even 50/50% split between the occupied and stratified zones is a reasonable starting point for most UFAD systems, and a 30/70% split between occupied and stratified zones is a reasonable starting point for true thermal displacement ventilation (DV) systems that gently “pour” a pool of cool air onto the floor (i.e., not using swirl diffusers).
1. UFAD System: Adjust the supply temperatures in the Room Design Airflows tab of the Loads Data spreadsheet for the Proposed UFAD HVAC system so that heat gain in the UFAD plenum will be accounted in the airflow calculation. In other words, the airflow calc needs to account for both the loads in the occupied zone and the load picked up by the supply air in the UFAD plenum. This is represented as an adjusted supply air temperature, and therefore a reduced delta-T, which will increase the design supply flow rate accordingly. The following example shows this adjustment as made by inserting a new column for UFAD supply plenum heat gain within the Room Design Airflows tab of the Loads Data spreadsheet for the UFAD system. The values for gain in degrees°F in the new column are simply added to the supply air temperature normally reported in the next column.

The plenum gain numbers can be set to typical values to begin with (e.g., 2–5 °F), and then later adjusted according to results of an initial system-level sizing run.

This adjustment of the supply air temperature for UFAD airflow should be done independent of the SAT and reset values for the AHU cooling coil entered in the System Parameters dialog. This dialog edits the system tabs of the corresponding Loads Data spreadsheet, and these values set the LAT at the AHU cooling coil, which will differ from the SAT at the diffusers. Because the coil LAT must be lower to address the heat gain in the UFAD plenum, and may need to be colder still for dehumidification, the AHU input parameters must be set independent of the zone SAT that is used for airflow calculations. Therefore, use the System Parameters dialog or direct editing of system design parameters on the relevant system tab, as shown below, to set the leaving temperatures for the AHU coils. Use the added column described above to adjust the SAT values for design airflow calculations.


The graph of HVAC node results for the sample UFAD model design sizing run below shows what you should look for upon completion of the system-level design sizing run (system-level design sizing for cooling will be the .cln results file, and in this case in Brisbane Australia January is the hottest month). Any simulation of the few hottest days year can be used for this test. The graph shows the significant difference between the SAT from the AHU at node 79 (dark blue line) and at the UFAD diffusers (node 59, light blue). The example spreadsheet above reflects the differences between the SAT at the AHU and diffusers for specific zones. These gains are somewhat greater than typical, given the hot sunny climate, significant direct-beam solar gain striking the raised floor top surface of the UFAD plenum, and the nature of the two-story test model (described in subsequent pages); however, not unrealistic.

The graph below is for the second system-level design sizing run—i.e., after adjusting the plenum gain values in the spreadsheet and re-applying the resulting zone airflow values to the controllers in the HVAC system. Node 60 (green) is the occupied zone temperature, which is the essential determinant of whether or not the airflow is adequately sized to address the zone loads with the actual supply temperature exiting the diffusers. Node 64 (red) is the stratified zone and node 78 (pink) is the RA plenum. It’s worth noting that the temperature in the first-floor RA plenum is actually lower than the temperature of the first-floor stratified zone, as the RA plenum air is being actively cooled by the second-floor UFAD supply plenum sitting on top of the metal and concrete floor deck that separates these two plenums.


2. Baseline system: Use either the same system model running the remixing path at all times or a dedicated system model, such as a standard VAV system, with the stratified zone and remixing path added. Thus the baseline system or any alternative version of the proposed that is not meant to be stratified can be modeled without removing the partitioning for thermal stratification from the thermal zones in the model. The multiplex region within the Baseline VAV system will exclude the UFAD supply plenum but will include the stratified zones in series with the occupied zones, with the re-mixing path “stirring” these back together as a single “well-mixed” zone. You must do two things:
a. Either, add the stratified zone, remixing path, and controller for this from the UFAD network to the Baseline or non-stratified alternate version, as shown below, or, to run the UFAD system model as a fully-mixed system for comparison, remove the AND connection from the controller on the re-mixing path in the UFAD version so it will run continuously during the simulation.
b. Zone-level loads for the occupied and stratified zones need to be combined for the autosizing of airflow controllers by adding a cell reference for this within the Loads Data spreadsheet for the system. This must be done for each Baseline or alternate non-stratified system in order to have the zone airflows properly sized to address the entire load with the space fully mixed.

This is actually quite simple. The example below shows the Loads Data spreadsheet for the Baseline VAV system in a model where the stratified zones where present at the time of zone-level autosizing. The formula in cells K8 through K11 have been modified to add the loads from cells J16 to 19, respectively. This will then size the design cooling airflow to the occupied zones according to the total load in occupied plus stratified zones. The same is done for the heating loads and airflow calculations. The controller airflow settings need to be updated (Assign System Parameters and Room Sizing Data in the workflow navigator) after combining the loads in the spreadsheet airflow calculation.


To get the stratified zones to show up in the spreadsheet in a list following the corresponding occupied zones, the stratified zones must first be organized in the model browser (normally by name) so that the sorted list of stratified zones will be exactly parallel to the corresponding occupied zones (same number of zone sin the exact same order). The stratified zones should be assigned to a group that matches the room group used to assign occupied zones to a particular AHU. Having done so, you must temporarily assign the appropriate group of stratified zones to the same ApacheHVAC system multiplex as the corresponding set of occupied zones (i.e., on additional rows below the occupied zones within the same multiplex edit dialog). Be sure not to rep[lace or delete multiplex rows for any occupied zones. Then run the zone-level sizing, which will generate a spreadsheet as shown above with the stratified zones listed below the occupied zones. If you already have baseline system spreadsheets that you want to keep, move them for the time being to a folder with a new (custom) name before running the zone-level sizing so that this will generate a new spreadsheet for each system. Then modify formula in the spreadsheet columns K and P on the Room Design Airflows tab so that the loads from occupied and stratified zones are added in these columns as described above. Once you have done all this, you will need to delete the added (stratified zone) layers from the HVAC system multiplex(es); however, be sure to leave the added rows in the spreadsheet. Thus, once having assigned to spreadsheet values to controls in ApacheHVAC, the airflow controllers on each occupied zone multiplex layer will have flow rates based upon the combined load, including the corresponding stratified zone for each.
The image below illustrates an appropriate test model for a very large building with numerous identical spaces served by a UFAD system. The divisions on the side of the model show occupied and stratified core and perimeter zones, common UFAD and RA plenums, and non-UFAD services zones at the back of the core zone. Apart from the one exterior façade, this small piece of the larger building is surrounded on all sides other zones. Whether they exist in the model or are represented by simplified dummy zones, these adjacent spaces are placed on a separate layer in ModelIt, and this layer is de-activated (status = off) in the Layer Properties dialog, thus making all the adjacencies effectively adiabatic (the thermal mass of the constructions is still present, but the net heat transfer across any adjacency is zero) without exposure to outdoor conditions. This allows much faster testing and experimentation for these representative zones.


The following are examples of the sort of results from a single hot day in an initial simulation run that should be checked to ensure that loads are being met and thermal stratification is being modeled as intended. This also illustrates how the modeling results can be used to explore and communicate the thermal effects associated with the assumed plume factors for internal gains.
 
 
 
Similar results can also be queried for nodes in the HVAC system to confirm system operation and to analyze the influence of both primary SA duct and UFAD plenum gains.
 
c. The raised floor top surface of the UFAD plenum sees direct-beam solar gain.
d. The UFAD plenum is sitting on a floor deck that has a warm return plenum below it, as in many multi-story projects.

In either of these two cases, there will be significant gain to the plenum, and thus the supply air temperature to the zone will not be the same as the leaving temperature from the AHU (regardless of whether you’re including duct heat gain). As the plenum area is generally large, gain to the plenum can be substantial. A study by the UC Berkeley Center for the Built Environment (CBE) showed that, even for a core zone, as much as 40% of cooling load for a typical multi-story office space with RA plenum below the floor deck can accrue to the supply air in the UFAD plenum before it reaches the diffusers. When direct beam solar is striking the raised floor, heat gain in the UFAD supply plenum can be much greater.

The remixing path is highlighted in yellow below. The controller for this is in red, including the logical AND connection to the fan-powered box controller, and the controller dialog is at right. The controller uses a simple proportional relationship to ramp up the re-mixing flow directly in proportion to the flow from the UFAD diffusers to the occupied zone.
 
 
 
The radiant fraction of an internal gain is seen by all “surfaces” in the space to which the gain is assigned. The term “surfaces” is in quotes here, as this includes the hole that connects the occupied and stratified zones in each room. As such, if, for example, the ceiling above and hole at the base of the stratified zone in a particular room were to account for 80% of the total “surface” area of that stratified zone, then 40% of the radiative energy would initially strike the ceiling and 40% would strike the hole as a “surface”. The remaining 20% would be distributed among the walls of the stratified zone in proportion to their surface area. In other words, as a proxy for actual view factors, which can get very computationally weighty, the radiant energy is distributed to surfaces as an area-weighted proportion of the total.
Once the radiative energy from the internal gain has been distributed, along with other radiative inputs, surface temperatures and the differences thereof are used to calculate radiant exchange between surfaces. When the hole as a pseudo “surface” between occupied and stratified zones receives radiation from the lights, it has no capacity to store thermal energy, and thus does not heat up and convectively heat the adjacent air as normal surfaces would; however, it does immediately communicate the radiation it receives to all of the surfaces that it can “see”. This re-distribution is done in proportion to surface area and temperature of receiving surfaces, as with other radiant exchanges. As such, the hole acts somewhat like a diffusing lens that scatters the radiation passing through it according the area and relative temperature of the surfaces it can see.