VEThermalTemplate

class iesve.VEThermalTemplate

Bases: object


add_air_exchange(ae: AirExchange) → None

Add an AirExchange object to the template


add_gain(gain: CasualGain) → None

Add a CasualGain object to the template


apply_changes() → None

Apply any changes made to the template to the model.

Note:

  • if this is not called, changes to the template will not be reflected in the model. This includes changes to gains and air exchanges for the template.

  • this operation may take a significant amount of time on large models


get() → tuple

Returns a tuple containing all the details for the thermal template. See the individual get_xxx functions below for information on the returned data.


get_air_exchanges() → list[AirExchange]

Returns a list of AirExchange objects


get_apache_systems() → dict

Dictionary containing Apache Systems settings. The following fields are returned:

Key

Description

aux_vent_system

(string) Aux vent system ID

aux_vent_system_same

(Bool) True if aux vent system is same as HVAC

system

cooling_capacity_units

(int) iesve.heating_cooling_capacity_unit

cooling_capacity_unlimited

(Bool)

cooling_capacity_value

(float) see cooling_capacity_units for units

cooling_plant_radiant_fraction

(float)

dhw_system

(string) DHW System ID

dhw_system_same

(Bool) True if DHW system is same as HVAC system

heating_capacity_units

(int) iesve.heating_cooling_capacity_unit

heating_capacity_unlimited

(Bool)

heating_capacity_value

(float) see cooling_capacity_units for units

heating_plant_radiant_fraction

(float)

HVAC_system

(string) HVAC System ID

system_air_free_cooling

(float) see system_air_free_cooling_units for units

system_air_free_cooling_units

(int) see below for airflow units

system_air_minimum_flowrate

(float) see system_air_minimum_flowrate_units for

units

system_air_minimum_flowrate_units

(int) see below for airflow units

system_air_variation_profile

(string) System air variation profile ID

Valid values for capacity units see iesve.heating_cooling_capacity_unit

Valid values for airflow units:

  • 0 = ach

  • 1 = l/s

  • 2 = l/s/m²

  • 3 = l/s/person


get_casual_gains() → list[CasualGain]

Returns a list of InternalGain objects.


get_room_conditions() → dict

Dictionary containing Room Conditions settings. The following fields are returned:

Key

Description

cooling_profile

(string) profile ID

cooling_setpoint

(float, °C) cooling setpoint, only valid if

cooling_setpoint_type is constant

cooling_setpoint_profile

(string) only valid if

cooling_setpoint_constant is False

cooling_setpoint_twovalue_main_setpoint

(float, °C) Two-value main setpoint

cooling_setpoint_twovalue_profile

(string) Two-value profile ID

cooling_setpoint_twovalue_setback

(float, °C) Two-value setback setpoint

cooling_setpoint_type

(setpoint_type) Setpoint type

dhw

(float) DHW value linked to dhw_units

dhw_profile

(string) ‘-’ if linked to occupancy, else

profile ID of DHW profile

dhw_units

(string) one of: l/(h·pers) or l/h

heating_profile

(string), profile ID

heating_setpoint

(float, °C) cooling setpoint, only valid if

heating_setpoint_type is True

heating_setpoint_profile

(string) only valid if

heating_setpoint_constant is False

heating_setpoint_twovalue_main_setpoint

(float, °C) Two-value main setpoint

heating_setpoint_twovalue_profile

(string) Two-value profile ID

heating_setpoint_twovalue_setback

(float, °C) Two-value setback setpoint

heating_setpoint_type

(setpoint_type) Setpoint type

plant_profile

(string) profile ID

plant_profile_type

(int) 0 = heating Profile, 1 = cooling profile,

2 = independent profile

sat_perc_lower

(float, %)

sat_perc_upper

(float, %)


remove_air_exchange(ae: AirExchange) → None

Remove air exchange from template. Will throw exception if air exchange is not associated with template.


remove_gain(gain: CasualGain) → None

Remove casual gain from template. Will throw exception if gain is not associated with template.


set(room_conditions: dict, system_data: dict) → None

Set both System Data and Room Conditions settings by passing in dictionaries of settings.

See iesve.VEThermalTemplate.set_apache_systems() and iesve.VEThermalTemplate.set_room_conditions() for dictionary keys.


set_apache_systems(**kwds)

Helper for @overload to raise when called.


set_room_conditions(**kwds)

Helper for @overload to raise when called.


name: str

Template description


standard: VEThermalTemplate_standard

Template standard



Enums

class iesve.VEThermalTemplate_standard(*values)

Bases: IntEnum


NCM = 1


NECB = 4


PRM_FloridaECB = 2


generic = 0


t24 = 3



class iesve.heating_cooling_capacity_unit(*values)

Bases: IntEnum


kilowatts = 0


unlimited = -1


watts_per_metre_squared = 1