Adaptive Comfort Criteria
For free running buildings the following three criteria, taken together, are used to assess the risk of overheating of buildings in the UK and Europe. A room or building that fails any two of the three criteria is classed as overheating.
- The first criterion sets a limit for the number of hours that the operative temperature can exceed the threshold comfort temperature (upper limit of the range of comfort temperature) by 1°K or more during the occupied hours of a typical non-heating season (1st May to 30th September).
- The second criterion deals with the severity of overheating within any one day, which can be as important as its frequency, the level of which is a function of both temperature rise and its duration. This criterion sets a daily limit for acceptability.
- The third criterion sets an absolute maximum daily temperature for a room, beyond which the level of overheating is unacceptable.
Further information on these criteria can be found in TM52 – 2013, section 6.1.2.