Manual Adjustment of Control Throttling Range for Tighter Control of Space Temperature and Humidity

Whereas space temperature controls for maintaining human thermal comfort typically have a deadband of several degrees between heating and cooling setpoints, plus an allowance for control of airflow, water, coils, etc. as the space temperature strays outside of the band defined by the setpoints, projects such as museum archives and laboratories may require considerably tighter controls.

The pre-defined controls and HVAC profiles require a minimum of 4°F (2.22 K) between the heating and cooling setpoints to avoid overlap of controls, and using this minimum value would provide zero actual deadband (one or the other control would always be active).
 
The graphic above from the ApacheHVAC user guide section 8.3.15 VAV airflow controls shows the relationship of the standard pre-defined control midbands and bandwidth relative to zone heating and cooling setpoints. In this example, the heating and cooling setpoints are separated by 6°F, and it can be seen that the ramps for cooling airflow and heating coil control will overlap if this difference is reduced by more than 2°F.

If you require tighter control than is allowed by the pre-defined controls, you must either 1) modify the HVAC control bandwidths and/or 2) modify the HVAC control profiles to move the control midband values closer to the setpoint, depending on the intended outcome. Appropriate controls sequencing—i.e., without overlap of controls such as airflow modulation and coil LAT modulation—usually requires that the bandwidth are reduced whenever the midband offset reduced. These operations are described below.