Humidity control — dehumidification, sub-cooling, and reheat to SAT

When working with a humid climate, it’s important to understand that the pre-defined systems are set up so that any zone with excessive RH can vote for a cooler off-coil temperature (down to the user input for Cooling coil min LAT) to dry the air at the AHU. If the System AHU Heating coil LAT value is set lower than the Cooling coil min LAT, this will for immediate reheat at the AHU when, and only when, the cooling coil LAT is driven below the heating coil LAT by demand for dryer air.
 
These four parameters will be more logically arranged in a future version. A display-only field will also be added to indicate the Min Cooling SAT from the AHU (uneditable) as the Min Cooling Coil LAT for zone cooling purposes that is coordinated with and thus determined by the AHU heating coil LAT.
 
A subsequent release will introduce revised means of translating system setpoints to controller inputs, and this will include user input parameters for control throttling range. This will facilitate modeling unusually tight control of space temperatures without having to manually customize the HVAC profiles.