NECB-2017 Article 8.4.4.19.(3)
Where the proposed building has ice-making loads along with simultaneous heating and/or service water heating loads, the reference building's ice plant shall be modelled with the following characteristics and components:
- a water-cooled, double-bundle water chiller having 100% heat-recovery capacity, where the energy model calculations do not allow for modelling of the ice plant and/or of heat recovery from the ice plant,
- operation and performance characteristics, such as efficiency, capacity, part-load performance and pumping flow rates, that are identical to those of the proposed building's machine,
- peak load and demand schedules that are identical to those of the proposed building, and
- heat rejection to
- at least one hydronic system for heating or service water heating, where the system has a load, and
ii) the atmosphere using a cooling tower defined in accordance with Articles 8.4.4.10. and 8.4.4.11., when the heat rejected is greater than the coincident heating load (see Note A-8.4.3.9.).