Fans

NECB-2017 Article 8.4.4.17 & Article 8.4.4.18

The following should be noted:
 
In the ApacheHVAC NECB systems library the fans have been setup to match the fan control specified in Table 8.4.4.7.B. The static pressure and efficiency have been included by default to match the requirements of 8.4.4.18 and the resulting fan power should match that obtained by using the power equation in section 5.2.3.

For variable volume fan control the part-load fan parameters have been setup to match the ‘fan power greater than 7.5 kW and less than 25 kW’ case. If the resulting fan power is greater than 25kW then the part load performance will have to be manually updated by the user to match the requirements in section 5.2.3 & article 8.4.4.17.