Table 6 Thermal Conductivity, Specific Heat Capacity and Density

 
System Material Database
 
Material  Description
Conductivity
Sp. Heat Capacity
Density
 
(W/mK)
(J/kgK)
(kg/m3)
Asphalts & Other Roofing Finishes
 
 
 
Asbestos Cement Decking
0.360
1050
1500
Asbestos Cement Sheet
0.360
1050
700
Asphalt
0.500
1000
1700
Felt/Bitumen Layers
0.500
1000
1700
Asphalt/Asbestos Tiles
0.550
837
1900
Roofing Felt
0.190
837
960
Asphalt Mastic Roofing
1.150
837
2325
Built-Up Roof – BR01
0.162
1464
1121
Roof Gravel/Slag – RG01
1.442
881
1674
 
 
 
 
 
 
 
 
Boards, Sheets & Deckings
 
 
 
Asbestos Cement Decking
0.360
1050
1500
Asbestos Cement Sheet
0.360
1050
700
Fibreboard
0.060
1000
300
Gypsum Plasterboard
0.160
840
950
Polyurethane Board
0.025
1400
30
Hardboard (Medium)
0.080
2000
600
Hardboard (Standard)
0.130
2000
900
Cork Board
0.040
1888
160
Chipboard
0.150
2093
800
Weatherboard
0.140
2000
650
Perlite Plasterboard
0.180
837
800
Cratherm Board
0.050
837
176
Anti-Sun Glass Cladding
1.050
750
2500
Plate-Glass Cladding
0.760
837
2710
4mm Clear Float Cladding
1.050
750
2500
Lightweight Metallic Cladding
0.290
1000
1250
Asbestos-Cement Board
0.580
1000
1900
Fibreboard – Tile & Lay-In Panel
0.058
600
290
Paperboard – Laminated
0.072
1400
480
Hardboard – Medium Density
0.105
1300
800
Paperboard – Homogeneous From Repulped Paper
0.072
1200
480
Hardboard – High Density
0.120
1300
880
Hardboard – Standard Tempered Grade
0.144
1300
1010
Particleboard – Low Density
0.102
1300
590
Particleboard – Medium Density
0.135
1300
800
Particleboard – High Density
0.170
1300
1000
Asbestos-Cement Board – AB01
0.597
837
1922
Cement Mortar – CM01
0.721
837
1858
Particle Board Underlay – PB04
0.311
1213
1202
Hard Board Medium Density Siding – HB01
0.094
1171
641
Hard Board Medium Density Others – HB02
0.105
1297
801
Hard Board High Density – HB03
0.118
1381
881
Hard Board High Density Standard Service Tempered – HB04
0.144
1381
1009
 
 
 
 
 
 
 
 
Brick & Block Work
 
 
 
Brickwork (Outer Leaf)
0.840
800
1700
Brickwork (Inner Leaf)
0.620
800
1700
Concrete Block (Heavyweight)
1.630
1000
2300
Concrete Block (Medium)
0.510
1000
1400
Concrete Block (Lightweight)
0.190
1000
600
Concrete Paviour
0.960
840
2000
Foam Slag
0.250
960
1040
Vermiculite Insulating Brick
0.270
837
700
Aerated Concrete Block
0.240
1000
750
Thermalite - High Strength
0.190
1050
760
Thermalite 'Turbo'
0.110
1050
480
Thermalite 'Shield'/'Smooth Face'
0.170
1050
650
Glass Block
0.700
837
2500
Common Brick – BK01
0.721
837
1922
Face Brick – BK04
1.310
921
2083
Face Brick – HF-A2
1.331
921
2083
Face Brick – HF-A7
1.331
921
2003
Common Brick – HF-C4
0.727
837
1922
 
 
 
 
 
 
 
 
Carpet
 
 
 
Wilton Carpet
0.060
1360
186
Simulated Sheeps Wool
0.060
1360
198
Wool Felt Underlay
0.040
1360
160
Cellular Rubber Underlay
0.100
1360
400
Synthetic Carpet
0.060
2500
160
 
 
 
 
 
 
Concrete
 
 
 
Aerated Concrete Slab
0.160
840
500
Cast Concrete (Dense)
1.400
840
2100
Cast Concrete (Lightweight)
0.380
1000
1200
Cast Concrete
1.130
1000
2000
Concrete Block (Heavyweight)
1.630
1000
2300
Concrete Block (Medium)
0.510
1000
1400
Concrete Block (Lightweight)
0.190
1000
600
Concrete Paviour
0.960
840
2000
Foam Slag
0.250
960
1040
Aerated Concrete Block
0.240
1000
750
Refactory Insulating Concrete
0.250
837
1050
Vermiculite Aggregate
0.170
837
450
Concrete Tiles
1.100
837
2100
Heavyweight Concrete Dried Aggregate – CC01
1.310
837
2243
Heavyweight Concrete Undried Aggregate – CC11
1.802
837
2243
Heavyweight Concrete Undried Aggregate – HF-C12
1.730
837
2243
Lightweight Concrete – 80 Lbs – CC21
0.36
837
1282
Lightweight Concrete – 30 Lbs – CC31
0.130
837
481
Lightweight Concrete – 40 Lbs – HF-C14
0.173
837
641
Lightweight Concrete – HF-C2
0.380
837
609
Heavyweight Concrete Block - Hollow – CB01
0.812
837
1618
Heavyweight Concrete Block - Concrete-Filled – CB02
1.310
837
2234
Heavyweight Concrete Block - Perlite-Filled – CB03
0.384
837
1650
Heavyweight Concrete Block – Part-Filled Concrete – CB04
1.011
837
1826
Heavyweight Concrete Block – Concrete and Perlite-Filled – CB05
0.825
837
1842
Mediumweight Concrete Block - Hollow – CB21
0.519
837
1218
Mediumweight Concrete Block - Concrete-Filled – CB22
0.771
837
1842
Mediumweight Concrete Block - Perlite-Filled – CB23
0.262
837
1250
Mediumweight Concrete Block – Part-Filled Concrete – CB24
0.572
837
1426
Mediumweight Concrete Block – Concrete and Perlite-Filled – CB25
0.431
837
1442
Lightweight Concrete Block - Hollow – CB41
0.384
837
1041
Lightweight Concrete Block - Concrete-Filled – CB42
0.639
837
1666
Lightweight Concrete Block - Perlite-Filled – CB43
0.220
837
1073
Lightweight Concrete Block – Part-Filled Concrete – CB44
0.486
837
1250
Lightweight Concrete Block – Concrete and Perlite-Filled – CB45
0.360
837
1266
 
 
 
 
 
 
 
 
Gravels, Beddings Etc.
 
 
 
Stone Chippings
0.960
1000
1800
Gravel
0.360
840
1840
Gravel-Based Soil
0.520
184
2050
Tile Bedding
1.400
650
2100
 
 
 
 
 
 
 
 
Insulating Materials
 
 
 
Eps Slab
0.035
1400
25
Silicon
0.180
1004
700
Glass-Fibre Quilt
0.040
840
12
Glass-Fibre Slab
0.035
1000
25
Mineral Fibre Slab
0.035
1000
30
Phenolic Foam
0.040
1400
30
Polyurethane Board
0.025
1400
30
Uf Foam
0.040
1400
10
Wood Wool Slab
0.100
1000
500
Vermiculite Insulating Brick
0.270
837
700
Refactory Insulating Concrete
0.250
837
1050
Glasswool
0.040
670
200
Thermalite - High Strength
0.190
1050
760
Thermalite 'Turbo'
0.110
1050
480
Thermalite 'Shield'/'Smooth Face'
0.170
1050
650
Siporex
0.120
1004
550
P.V.C
0.160
1004
1379
Polystyrene
0.030
1380
25
Hard Rubber
0.150
1000
1200
Cratherm Board
0.050
837
176
Uf Foam Two
0.030
1764
30
Uf Foam Two
0.030
1764
30
Lightweight Metallic Cladding
0.290
1000
1250
Dense Eps Slab Insulation (styrofoam)
0.025
1400
30
Cellular Glass
0.050
800
136
Glass-Fibre – Organic Bonded
0.036
1000
100
Expanded Perlite – Organic Bonded
0.052
1300
16
Expanded Rubber - Rigid
0.032
1700
72
Cellular Polyurethane
0.023
1600
24
Cellular Polyisocyanurate
0.023
900
32
Cellular Phenolic – Mineral Fibre With Resin Binder
0.042
700
240
Cement Fibre Slab – Shredded Wood With Magnesia Oxysulfide Cement Binder
0.082
1300
350
Vermiculite - Exfoliated
0.068
1300
120
Felt & Membrane – Felt – HF-E3
0.190
1674
1121
Felt & Membrane – Finish – HF-A6
0.415
1088
1249
Mineral Wool/Fibre – Batt – IN01
0.043
837
10
Mineral Wool/Fibre – Fill – IN11
0.046
837
10
Mineral Wool/Fibre – Fill – IN12
0.046
837
11
Cellulose Fill – IN13
0.039
1381
48
Insulation Board – HF-B2
0.043
1381
48
Insulation Board – HF-B5
0.043
837
32
Preformed Mineral Board – IN21
0.042
711
240
Expanded Polystyrene – IN31
0.035
1213
29
Expanded Polyurethane – IN41
0.023
1590
24
Urea Formaldehyde – IN51
0.035
1255
11
Insulation Board Sheathing – IN61
0.055
1297
288
Insulation Board Shingle Backer – IN63
0.058
1297
288
Insulation Board Nail Base Sheathing – IN64
0.064
1297
400
Preformed Roof Insulation – IN71
0.052
837
256
 
 
 
 
 
 
 
 
Metal
 
 
 
Steel
50.000
480
7800
Copper
200.000
418
8900
Aluminium
160.000
896
2800
Lightweight Metallic Cladding
0.290
1000
1250
Steel Siding – HF-A3
44.970
418
7690
 
 
 
 
 
 
 
 
Plaster
 
 
 
Plaster (Dense)
0.500
1000
1300
Plaster (Lightweight)
0.160
1000
600
Gypsum Plasterboard
0.160
840
950
Perlite Plasterboard
0.180
837
800
Gypsum Plastering
0.420
837
1200
Perlite Plastering
0.080
837
400
Vermiculite Plastering
0.200
837
720
Plaster Ceiling Tiles
0.380
840
1120
Cement Plaster
0.720
800
1860
Perlite Plaster
0.220
1300
720
Perlite Plaster – Sand Aggregate
0.810
800
1680
Cement Plaster – With Sand Aggregate – CM03
0.721
837
1858
Gypsum/ Plaster Board – HF-E1
0.160
837
801
Gypsum Plaster Lightweight Aggregate– GP04
0.230
837
721
Gypsum Plaster – Sand Aggregate– GP06
0.819
837
1682
 
 
 
 
 
 
 
 
Screeds And Renders
 
 
 
External Rendering
0.500
1000
1300
Screed
0.410
840
1200
Granolithic Render/Screed
0.870
837
2085
Stucco – HF-A1
0.721
837
2659
 
 
 
 
 
 
 
 
Sands, Stones And Soils
 
 
 
Stone Chippings
0.960
1000
1800
Gravel
0.360
840
1840
Gravel-Based Soil
0.520
184
2050
Sandstone
1.830
712
2200
Granite (Red)
2.900
900
2650
Marble (White)
2.770
802
2600
Cultivated Sandy Soil 12.5%D.W. Moisture
1.790
1190
1800
Cultivated Sandy Soil 25.0%D.W. Moisture
2.220
1480
2000
Cultivated Clay Soil 12.5%D.W. Moisture
1.180
1250
1800
Cultivated Clay Soil 25.0%D.W. Moisture
1.590
1550
2000
Cultivated Peat Soil 133%D.W. Moisture
0.290
3300
700
Cultivated Peat Soil 366%D.W. Moisture
0.500
3650
1100
Dry Limestone Sub-Soil
1.490
840
2180
London Clay
1.410
1000
1900
Soil
1.729
837
1842
Stone – ST01
1.802
837
2243
Stone – HF-A3
1.435
1674
881
Terrazzo – TZ01
1.802
837
2243
 
 
 
 
 
 
 
 
Tiles
 
 
 
Clay Tile
0.840
800
1900
Concrete Tiles
1.100
837
2100
Slate Tiles
2.000
753
2700
Plastic Tiles
0.500
837
1950
Rubber Tiles
0.300
2000
1600
Cork Tiles
0.080
1800
530
Asphalt/Asbestos Tiles
0.550
837
1900
P.V.C./Asbestos Tiles
0.850
837
2000
Ceiling Tiles
0.056
1000
380
Plaster Ceiling Tiles
0.380
840
1120
Lightweight Metallic Cladding
0.290
1000
1250
Acoustical Tile – Mineral Fibreboard
0.050
800
290
Acoustic Tile  - AC01
0.057
1339
288
Acoustic Tile – HF-E5
0.061
2142
480
Hollow Clay Tile – 1 Cell – CT01
0.498
837
1121
Hollow Clay Tile – 2 Cells – CT03
0.571
837
1121
Hollow Clay Tile – 3 Cells – CT06
0.692
837
1121
Clay Tile – HF-C1
0.571
837
1121
Paver – Clay Tile – CT11
1.802
837
1922
Slate – SL01
1.442
1464
1602
 
 
 
 
 
 
 
 
Timber
 
 
 
Timber Flooring
0.140
1200
650
Plywood (Lightweight)
0.150
2500
560
Plywood (Heavyweight)
0.150
1420
700
Wood Blocks
0.140
1200
650
Wood Wool Slab
0.100
1000
500
Hardboard (Medium)
0.080
2000
600
Hardboard (Standard)
0.130
2000
900
Pine (20% Moist)
0.140
2720
419
Cork Board
0.040
1888
160
Chipboard
0.150
2093
800
Weatherboard
0.140
2000
650
Oak (Radial)
0.190
2390
700
Cork Tiles
0.080
1800
530
Plywood – PW01
0.115
1213
545
Soft Wood – WD01
0.115
1381
513
Hard Wood – WD11
0.158
1255
721
Wood – HF-B7
0.121
837
593
Plywood – Douglas Fir
0.120
1200
540
Shingle Wood – WS01
0.115
1255
513
 
Table 7  Reflectance, Absorbtance and Transmittance of Glazing Materials
 
Description
Refl
Absorp
Trans
Refr
 
 
 
 
 
Clear Float 4mm
0.07
0.11
0.82
1.526
Clear Float 6mm
0.07
0.15
0.78
1.526
Clear Float 10mm
0.07
0.23
0.7
1.526
Clear Float 12mm
0.06
0.27
0.67
1.526
'Spectrafloat' 6mm 51/65 (Bronze)
0.1
0.36
0.54
1.526
'Antisun' Float 6mm 72/62 (Green)
0.05
0.49
0.46
1.526
'Antisun' Float 4mm 55/68 (Grey)
0.05
0.4
0.55
1.526
'Antisun' Float 6mm 42/60 (Grey)
0.05
0.53
0.42
1.526
'Antisun' Float 10mm 25/49 (Grey)
0.04
0.71
0.25
1.526
'Antisun' Float 12mm 19/45 (Grey)
0.04
0.77
0.19
1.526
'Antisun' Float 4mm 61/70 (Bronze)
0.06
0.36
0.58
1.526
'Antisun' Float 6mm 50/62 (Bronze)
0.05
0.49
0.46
1.526
'Antisun' Float 10mm 33/51 (Bronze)
0.04
0.67
0.29
1.526
'Antisun' Float 12mm 27/47 (Bronze)
0.04
0.73
0.23
1.526
'Antisun' Float  6mm 54/62 (Blue)
0.05
0.49
0.46
1.526
Reflectafloat 6mm 35/53 (Silver)
0.28
0.29
0.43
1.526
'Suncool' Classic 6mm 20/33 (Blue)
0.21
0.64
0.15
1.526
'Suncool' Classic 6mm 30/39 (Blue)
0.18
0.61
0.21
1.526
'Suncool' Classic 6mm 40/50 (Blue)
0.1
0.58
0.32
1.526
'Suncool' Classic 6mm 10/24 (Bronze)
0.21
0.73
0.06
1.526
'Suncool' Classic 6mm 10/23 (Silver)
0.32
0.6
0.08
1.526
'Suncool' Classic 6mm 20/34 (Silver)
0.18
0.66
0.16
1.526
'Suncool' Classic 10mm 10/33 (Blue)
0.19
0.66
0.15
1.526
'Suncool' Classic 10mm 30/38 (Blue)
0.17
0.63
0.2
1.526
'Suncool' Classic 10mm 40/49 (Blue)
0.09
0.6
0.31
1.526
'Suncool' Classic 10mm 10/24 (Bronze)
0.19
0.76
0.05
1.526
'Suncool' Classic 10mm 10/23 (Silver)
0.3
0.62
0.08
1.526
'Suncool' Classic 10mm 20/34 (Silver)
0.16
0.69
0.15
1.526
'Suncool' Classic  6mm 20/34 (Silver)
0.18
0.66
0.16
1.526
'Suncool' Classic 10mm 20/33 (Blue)
0.19
0.66
0.15
1.526
Stopsol 4mm (Clear)
0.25
0.22
0.53
1.526
Stopsol 5mm (Clear)
0.25
0.24
0.51
1.526
Stopsol 6mm (Clear)
0.25
0.25
0.5
1.526
Stopsol 8mm (Clear)
0.25
0.28
0.47
1.526
Stopsol 10mm (Clear)
0.24
0.31
0.45
1.526
Stopsol 4mm (Bronze)
0.27
0.38
0.35
1.526
Stopsol 5mm (Bronze)
0.27
0.41
0.32
1.526
Stopsol 6mm (Bronze)
0.26
0.45
0.29
1.526
Stopsol 8mm (Bronze)
0.26
0.51
0.23
1.526
Stopsol 10mm (Bronze)
0.26
0.56
0.18
1.526
Stopsol 6mm (Silver)
0.2
0.37
0.43
1.526
Kappafloat 4mm (Champagne)
0.17
0.22
0.61
1.526
Kappafloat 4mm (Neutral)
0.2
0.14
0.66
1.526
Kappafloat 6mm (Champagne)
0.16
0.26
0.58
1.526
Kappafloat 6mm (Neutral)
0.2
0.17
0.63
1.526
Saflex Blue-Green (Light) 5.4mm
0.07
0.19
0.74
1.526
Saflex Blue-Grey (Light) 5.4mm
0.06
0.4
0.54
1.526
Saflex Blue-Grey (Medium) 6.2mm
0.05
0.59
0.36
1.526
Saflex Bronze 5.4mm
0.06
0.41
0.53
1.526
Saflex Bronze (Light) 5.4mm
0.06
0.37
0.57
1.526
Saflex Bronze (Medium) 5.7mm
0.05
0.56
0.39
1.526
Saflex Green-Blue (Light) 5.3mm
0.07
0.18
0.75
1.526
Saflex Grey 5.4mm
0.05
0.51
0.44
1.526
Saflex Grey-Green (Light) 5.4mm
0.06
0.42
0.52
1.526
Saflex Marine Blue (Light) 5.3mm
0.06
0.35
0.59
1.526
Saflex Marine Blue (Medium) 5.3mm
0.05
0.56
0.39
1.526
Saflex Pink (Light) 6.3mm
0.06
0.31
0.63
1.526
Saflex Translucent White 6.1mm
0.06
0.37
0.57
1.526
Saflex Shadowlite Smoke Brown (L) 5.4mm
0.06
0.39
0.55
1.526
Saflex Shadowlite Smoke Brown (M) 5.3mm
0.05
0.67
0.28
1.526
Saflex Shadowlite Smoke Brown (D) 6.3mm
0.04
0.86
0.1
1.526
Polycarbonate 3mm Clear
0.09
0.09
0.82
1.6
Acrylic 3mm Clear
0.09
0.06
0.85
1.49
Luxguard 6mm (Bright Silver) Cs-14
0.27
0.61
0.12
1.526
Luxguard 6mm (Bright Silver) Cs-20
0.22
0.61
0.17
1.526
Luxguard 6mm (Bright Silver) Cs-35
0.14
0.54
0.32
1.526
Luxguard 6mm (Pewter) Cp-14
0.2
0.66
0.14
1.526
Luxguard 6mm (Pewter) Cp-20
0.16
0.65
0.19
1.526
Luxguard 6mm (Pewter) Cp-35
0.09
0.58
0.33
1.526
Luxguard 6mm (Bronze) Cb-14
0.18
0.69
0.13
1.526
Luxguard 6mm (Bronze) Cb-20
0.13
0.68
0.19
1.526
Luxguard 6mm (Bronze) Cb-35
0.08
0.6
0.32
1.526
Luxguard 6mm (Royal Blue) Cr-14
0.17
0.7
0.13
1.526
Luxguard 6mm (Royal Blue) Cr-20
0.12
0.69
0.19
1.526
Luxguard 6mm (Royal Blue) Cr-35
0.07
0.61
0.32
1.526
Thermoclear 8mm Polycarbonate Sheeting
0.05
0.8
0.15
1.59
Thermoclear 16mm Polycarbonate Sheeting
0.08
0.7
0.22
1.59
Perfectly Clear Glazing Material
0
0
1
1
 
Note:
 
The figures for Kappafloat are for viewing the glass from the coated side, i.e. when the Kappafloat is the inside pane.  If the Kappafloat is used as the outside pane then values should be obtained from another source.
The Saflex and Saflex Shadowlite glasses are laminated glass with a 0.38mm interlayer
The refractive index for the plastic materials listed (GRP, PC) will NOT be the same as for glass.
 
Sources of above data:
 
Pilkington, Transmission Properties of Windows  July 85 Glaverbel, Reflective Glazing Monsanto, Solar Control J.Page and R.Lebens, Climate in the United Kingdom.