Appendix A. Comparison between L2 England 2013 and 2021

This appendix provides a summary of the changes between 2013 & 2021 iterations of L2A.
 
Headlines:
        
·         Reduce emissions by 27% (non-domestic on average)
·         CO2 target (TER) plus new primary energy target (TPER)
·         Notional building U values tightened
·         New emission factors including for electricity monthly values
·         New emission factors for heat networks
·         New Part O (overheating) for residential elements
·         Solar gain checks for non-residential spaces
·         1000m2 non-residential buildings need to produce a TM54 energy forecast
·         CIBSE 2016 TRY weather files are to be used in place of 2006
(Affects thermal/energy simulations and solar gain limit targets)
·         Weather files upgraded to DSY1 for Part O overheating simulation
 
Key details:
·         Side & top-lit space types now affect notional fabric
·         High & low hot water demand classification added
·         Notional building heating fuel as actual
·         Notional building U values tightened
·         Notional non-repeating thermal bridging allowance is 10% (actual is 25%)
·         Notional building now includes PVs (unless heat pump)
·         Revised approach for determining the illuminance level for a zone in the Notional building
·         Revised approach for accounting for primary energy due to electricity generated on-site by renewables
·         Updated options for HVAC systems (added added ‘VRF’ and ‘Chilled ceilings or passive chilled beams and mixing ventilation’ )
·         Calculation of the corresponding fan energy
·         Revised approach for calculating the fan energy associated with demand control of ventilation
·         Emission factors for electricity values are now monthly
·         New grid displaced PV energy source added
·         New district heating values (still as single input value for CO2 Factor & Primary Energy factor)
·         In the AB you specify new/existing  district heating this influences NB factors directly
 
Notional building details:
·         Size, shape, zoning, topographical shading & weather is the same as the actual building as 2013
·         Local shades are ignored
·         Openings  are generated with the same dimensions as 2013
·         Non-repeating thermal bridging allowance is 10% (actual is 25%)
·         Air permeability tightened to 3 & 5 m3/h.m2 at 50Pa (side/unlit & top-lit)
·         Aux energy: pump power density is the same as 2013
·         Aux energy: fan pump power density is the same as 2013 except for HEPA filters (Hosp_OpTheatre)
·         Aux energy: local mechanical exhaust is the same as 2013
·         Power factor is the same as 2013
·         PVs included based on equation 9 but reduced if heating demand is met with a heat pump (100% demand met means no PV in NB)
·         Lighting design illuminance: set as the Actual building but clamped to the maximum or minimum illuminance as per activity (template)
·         The general lighting  is based on lighting with efficacy of 95 luminaire lumens per circuit-watt; so a notable tightening over 2013 value of 60
·         Display lighting LPD:  luminous efficacy of 95 light source lumens per circuit-watt so the display lighting power density in the Notional zone will be from the NCM Activity Database multiplied by 0.158 (2013 was 0.682)
·         Parasitic power density to 0.1 W/m2 for photoelectric or occupancy dimming control (2013 was 0.3)
·         U values overall tighter for side & unlit activities; windows at 1.4, although top-lit roof-lights are more generous at 2.1
·         Thermal capacity is light / very lightweight
·         Construction details (app A): layers have been updated
·         Heating fuel & efficiency set by the actual building
·         High & low hot water demand classification &  actual fuel sets notional seasonal efficiency, fuel & if-storage for notional building DHW
·         Cooling SSEER is revised and heat recovery efficiency is revised
 
Actual building details:
·         Non repeating thermal bridging allowance + 25% (notional & reference 10%)
·         Pump power densities the same as 2013 but new entries for VRF / chilled ceilings
·         Fan power density equation 15 has changed (now x 0.85)
·         Lighting design illuminance must be pro rated to NCM minm. in activity database when less than the NCM minm.
·         Lighting inference:  luminaire luminous efficacy value of 95 (2013 uses 60)
·         Demand control ventilation aux energy adjustment has been revised
·         Modular & potable buildings TER & TPER factors revised
·         Criterion 3 limiting solar gains: benchmark glazing g-values and for type 3 area have been reduced (type 1&2 where 0.68 in 2013)
 
 Reference building details:
·         Definition is the same as 2013
·         Construction U values & thermal mass are the same as 2013
·         Non-repeating thermal bridges allowance 10% same as 2013
·         HVAC now defines all spaces as naturally ventilated with the same 27degC cooling setpoint as 2013
·         The HWS seasonal efficiency is the same as 2013
·         Lighting illuminance level is defined similar to that for the notional building; the W/m2. 100 lux values are the same as 2013
·         Manual switching is defined the same as 2013