×
Menu
Index

10.4 Results

This section outlines the rooms that pass, fail and those that are unoccupied.
 
Each room is tested for occupied hours; hours in different operational modes are tested separately.
Each room must pass the tests in both operational modes to pass.
 
A room that fails any two of the three free-running overheating criteria is classed as overheating and thus fails the BB101 adaptive check.
 
A room that simply fails the PMV mechanically ventilated / cooled overheating criteria is classed as overheating and thus fails the BB101 mechanically ventilated / cooled check.
 
A room that fails any of the three free-running CO2 criteria is classed as having inadequate air quality and thus fails the BB101 free-running air quality check.
 
A room that fails any of the two mechanically ventilated / cooled CO2 criteria is classed as having inadequate air quality and thus fails the BB101 mechanically ventilated / cooled air quality check.