7 CO2 Criteria

For free running mode occupied timesteps:
·         CO2 maximum daily average (<1500ppm)
  Average CO2 all occupied timesteps per day Jan-Dec inclusive.
  Find max average day.
  Test max average day against threshold.
·         Peak (<2000ppm consecutive 20 mins/day*)
  Peak CO2 all occupied 20 min chunks Jan-Dec inclusive.
  Find max peak.
  Test max peak against relevant threshold.
·         And achieve for the majority of the time:
New build 1200 PPM (800 ppm above OA)
Refurb 1750 PPM (1350ppm above OA)
 
  Average CO2 all occupied timesteps Jan-Dec inclusive.
  Test average against relevant threshold.
 
*The max 20 mins test requires Apachesim to be set with a 10-minute simulation timestep.