In the NECB navigator the reference constructions are created via the ‘Generate Reference’ action further down the navigator workflow.
 
The ‘Generate Reference’ action creates a series of project specific reference constructions based on the construction makeup of the associated proposed model and the following NECB rules:
 
·        Reference envelope thermal transmittance is determined from NECB 2011 Part 3 Building Envelope Table 3.2.2.2, Table 3.2.2.3, Table 3.2.2.4 and Table 3.2.3.1.
·        NECB 2011 Section A-3.3.4.9(4)(d) states that the reference building envelope assemblies should follow the layer structure of the proposed building’s envelope assemblies (type and order) but the insulation thickness should be varied to match the maximum overall thermal transmittance as referenced above.
·        NECB 2011 Section 3.3.4.10(5) states that the thermal mass shall be set to "light-weight," which corresponds to a framed exterior wall or a 51 mm concrete floor slab (150 kg/m2 of floor area). NECB 2011 Section 8.4.4.5(1) also states that the thermal characteristics of the reference building's building envelope assembly shall be modeled as being identical to those of lightweight construction. Thus it can be concluded that the 'light-weight' requirement applies to external walls, ground contact floors and roofs.
 
Based on these rules the following methodology is used to create the reference constructions: