×
Menu
Index

Methods Defined Here

 
add_air_exchange(airExchange)
Add an AirExchange object to the template.
 
add_gain(casualGain)
Add a CasualGain object to the template.
 
apply_changes()
Apply any changes made to the template to the model.  Note: if this is not called, changes to the template will not be reflected in the model.  This includes changes to gains and air exchanges for the template.
Note – this operation may take a significant amount of time on large models.
 
get() -> (roomConditions, apSystems, casualGains, airExchanges)
Returns a tuple containing all the details for the thermal template.
See the individual get_xxx functions below for information on the returned data.
 
get_air_exchanges() -> list
Returns a list of AirExchange objects.
 
get_apache_systems() -> dictionary
Dictionary containing Apache Systems settings. The following fields are returned:
 
aux_vent_system
(string) Aux vent system ID
aux_vent_system_same
(Bool) True if aux vent system is same as HVAC system
cooling_capacity_units
(int) see below
cooling_capacity_unlimited
(Bool)
cooling_capacity_value
(float) see cooling_capacity_units for units
cooling_plant_radiant_fraction
(float)
dhw_system
(string) DHW System ID
dhw_system_same
(Bool) True if DHW system is same as HVAC system
heating_capacity_units
(int) see below
heating_capacity_unlimited
(Bool)
heating_capacity_value
(float) see cooling_capacity_units for units
heating_plant_radiant_fraction
(float)
HVAC_system
(string) HVAC System ID
system_air_free_cooling
(float) see system_air_free_cooling_units for units
system_air_free_cooling_units
(int) see below for airflow units
system_air_minimum_flowrate
(float) see system_air_minimum_flowrate_units for units
system_air_minimum_flowrate_units
(int) see below for airflow units
system_air_variation_profile
(string) System air variation profile ID
 
Valid values for capacity units:
   -1 = unlimited
   0 = kW
   1 = W/m2
 
Valid values for airflow units:
    0 = ach
    1 = l/s
    2 = l/s/m²
    3 = l/s/person
 
get_casual_gains() -> list
Returns a list of InternalGain objects.
 
get_room_conditions() -> dictionary
Dictionary containing Room Conditions settings.  The following fields are returned:
 
cooling_profile
(string) profile ID
cooling_setpoint
(float, °C) cooling setpoint, only valid if cooling_setpoint_constant is True
cooling_setpoint_constant
(Bool)
cooling_setpoint_profile
(string) only valid if cooling_setpoint_constant is False
dhw
(float) DHW value linked to dhw_units
dhw_profile
(string) '–' if linked to occupancy, else profile ID of DHW profile
dhw_units
(string) one of:  l/(h·pers) or l/h
heating_profile
(string), profile ID
heating_setpoint
(float, °C) cooling setpoint, only valid if heating_setpoint_constant is True
heating_setpoint_constant
(Bool)
heating_setpoint_profile
(string) only valid if heating_setpoint_constant is False
plant_profile
(string) profile ID
plant_profile_type
(int) 0 = heating Profile, 1 = cooling profile, 2 = independent profile
sat_perc_lower
(float, %)
sat_perc_upper
(float, %)
 
remove_air_exchange(airExchange)
Remove air exchange from template.  Will throw exception if air exchange is not associated with template.
 
remove_gain(casualGain)
Remove casual gain from template.  Will throw exception if gain is not associated with template.
 
set (room_conditions, system_data)
    Set both System Data and Room Conditions settings by passing in dictionaries of settings.
    See set_apache_systems and set_room_conditions for dictionary keys.
 
set_apache_systems(system_data)
    Set System Data settings by passing in a dictionary of settings.
    Dictionary keys are:
 
aux_vent_system
aux_vent_system_same
conditioned
cooling_capacity_units
cooling_capacity_value
cooling_plant_radiant_fraction
dhw_system
dhw_system_same
heating_capacity_units
heating_capacity_value
heating_plant_radiant_fraction
HVAC_methodology
HVAC_system
system_air_free_cooling
system_air_free_cooling_units
system_air_minimum_flowrate
system_air_minimum_flowrate_units
system_air_variation_profile
 
 
set_room_conditions(room_conditions)
Set Room Conditions settings by passing in a dictionary of settings.
Dictionary keys are:
 
cooling_profile
cooling_setpoint
cooling_setpoint_constant
cooling_setpoint_profile
dhw
dhw_profile
dhw_units
heating_profile
heating_setpoint
heating_setpoint_constant
heating_setpoint_profile
plant_profile
plant_profile_type
sat_perc_lower
sat_perc_upper