×
Menu
Index

Room Unit Controllers

 
Room unit controllers provide control over the particular device or unit instance with which they’re associated. In the case of “radiators” and “chilled ceilings,” controls include scheduling of on/off operation by time-switch profiles, on/off control according to sensed variables, and proportional control of water temperature and/or flow rate according to sensed variables. One surface temperature sensor per zone, as described under sensed variables, is available for use with on/off or proportional controls.
 
Figure 7 - 1 : Room component dialog, including facilities for selecting defined Room Units and examples of unit types (note that this is for illustration only, as it would be very unusual to place room units from all three categories in a single space within the model).
 
Individual instances of a Room unit Type are indicated within the Room component dialog. The type must be defined before this action will be available for a given category of room unit. A “Room” component can represent any occupied or unoccupied 3D space in the model, including normal rooms or thermal zones, façade cavities, supply plenums, and heated or cooled ceiling or floor slabs. User-defined types are effectively sitting on a shelf—they are not active until an instance of the defined type is placed within a Room component. Each time a room unit type is placed within a room component, an additional instance of that type is created. Room unit controllers are thus specific separate instances of a particular room unit type. Note that no more than one room unit instance per category (e.g., Radiators) may be placed within a given room component; however, for Radiators and Chilled ceilings, it is possible via their respective controller dialogs to specify multiple copies of the unit for any given instance. Thus, it is possible to have many identical radiators or chilled ceilings in particular model space using a single instance of the type.
 

Hot Water Radiator Control

In ApacheHVAC, the term “Radiators” covers a broad range of hydronic heating devices placed directly in conditioned spaces. These generally include cast-iron radiators, radiant panel heaters, fin-tube convectors, and so forth. Radiators can also be used as a hydronic loop within a heated slab zone, but care should be taken in such cases to appropriately define the “type” using parameters that will represent the properties of just the hydronic loop within the slab.
Figure 7 - 2 : Radiator control dialog with illustrative inputs for a fin-tube hydronic baseboard heater using a constant set-point temperatures for thermostatic on-off control, a fixed supply water temperature, and proportional control of water flow rate to modulate the output of the device (the HP3 profile provides a proportional midband value that is linked to user inputs for the occupied hours setpoint and setback value for unoccupied hours). The sensors for on-off and proportional controls have been located in the local room; however, they can be located in other spaces or outside of the building.
 
Reference
Enter a description of the controller. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers.
Radiator type reference
Select a radiator device for placement in the room from the list of previously defined types.
Number of units
Enter the number of copies of this radiator or heating panel instance to be included within the associated space. This can be any number between 0 and 1,000, including non-integer values and values less than 1.0, but excluding 0. This parameter provides for the scaling of a defined room unit type as applied to spaces with differing loads. For example, a Radiator type with heat output of 1.0 kW at design conditions can be defined as a type, and a room or thermal zone requiring 7.8 kW of heat at design conditions can use 7.8 units of this type.
Heat source
Select the reference of the previously defined heat source from list, which will serve the radiator placed in the room from the radiators list.
On/off and set point controls
Flow for Maximum Control Signal
Enter the flow rate that corresponds to the maximum control signal from the controller. If no proportional control is to be used, enter the flow rate that occurs whenever this radiator is on. Regardless of the number of units included (see section 7.1.1.3 Number of units, above), the water flow rate specified should be for exactly one unit.
For reverse-acting proportional control where the sensed variable is room temperature (typical for heating devices), this value will be lower than that in the water temperature at minimum control signal, and may be zero if the flow modulation device being modeled is capable of modulating down to zero flow.
 
Warning Limits (l/s)
0.001 to 2.5
Error Limits (l/s)
0.0 to 99.0
Water Temperature for Maximum Control Signal
Enter the water temperature which corresponds to the maximum control signal from the controller. If no proportional control was specified, enter the temperature of the radiator supply water. Note that for reverse-acting proportional control where the sensed variable is room temperature (typical for heating devises), this value is lower than that in the water temperature at minimum control signal. This parameter is not used when “Use hot water loop supply temperature?” is checked.
 
 
Warning Limits ( ° C)
30.0 to 85.0
Error Limits ( ° C)
0.0 to 250.0
Use hot water loop supply temperature
Selecting this option sets the radiator or heating panel water temperature to the supply temperature of the connected Hot water loop. The radiator or heating panel will therefore also see any change in hot water loop supply temperature resulting from loop supply temperature reset controls or off-design supply temperatures resulting from an undersized boiler or similar capacity limitation.
This option is available only when the radiator has proportional flow control enabled and is served by a hot water loop. It is not available with proportional temperature control, which would be used in lieu of this option for the purpose of modeling a zone-level mixing valve capable of moderating the water temperature supplied to this heating device.
Time switch profile
Specify the time switch profile that will be used to schedule the operation of the controller.
Sensor location
The sensor may be internal (contained in a room or on a surface in a room) or external. An external sensor would be the equivalent of a weather compensated system or outdoor temperature reset. Several radiators may use the same internal sensor—e.g., all rooms on the west façade of a building may be controlled by a single sensor. As would be appropriate for a hydronic loop in a conditioned slab, one surface temperature sensor per zone is available for use with on/off or proportional controls. The surface vs. zone location of the sensor is determined by selection of the sensed variable and tagging of the sensed surface within the Apache Thermal view. For more information on using surface temperature sensors, see section 6.3.2 Sensed variables.
Select an appropriate sensor location.
Sensed variable
Select the variable that is to be used in the on/off (set point) control.
Surface temperature is available as a sensed variable for use with on/off or proportional controls, as would be appropriate for a hydronic loop in a conditioned slab. The surface vs. zone location of the sensor is determined by selection of the sensed variable.  The specific surface adjacency for the sensor location must also be tagged within the Apache Thermal view. For more information on using surface temperature sensors, see section 6.3.2 Sensed variables.
Note: While Flow rate is on the Room Unit controller selection list of Sensed variables and does cause gpm or l/s units to be displayed, this sensed variable is not yet available for Room Unit controllers.
Radiant fraction
When the sensed variable is dry-bulb temperature, an input field is available to set the radiant fraction of sensed temperature. As an example, if the radiant fraction were set to 0.5, the sensor would effectively be sensing dry resultant temperature—i.e., operative temperature in still air conditions. 
Enter an appropriate value for a radiant fraction.
Set point variation
The set point for on/off control may be Constant or Variable. Select Constant or Timed as appropriate
Set point or variation profile
Enter a fixed setpoint value when the set point is Constant or select a timed profile when the setpoint variation is timed. This can be a formula profile.
Deadband
Deadband defines the controller hysteresis or range of sensed variable values over which switching occurs in on/off control (see section 6.6.3.4 ).
Enter an appropriate deadband value.
High sensor input (resulting on/off action)
This parameter relates to on/off (set point) control and specifies whether the switching signal output by the controller is ON or OFF for high values of the sensed variable. (See section 6.6.3.5 ).
Enter the appropriate sensor input.
Proportional controls for water flow rate and temperature
Both proportional flow and temperature controls are provided. To minimize redundant explanations, however, the inputs that are identical for these two types of proportional control will be described just once in the following subsections.
Proportional Flow Controller
Tick the box next to this item to use proportional control of the water flow rate in the radiator. Then click on the item to enter and edit parameters for the proportional controller. If proportional control of water flow rate is not used, the water flow rate will be fixed at the value given in the “Flow at Max Control Signal” input.
Proportional Temperature Controller
Tick the box next to this item to use proportional control of the water temperature in the radiator. Then click on the item to enter and edit parameters for the proportional controller. If proportional control of water temperature is not used, the water temperature will be fixed at the value given in the “Temp at Max Control Signal” input.
Sensor location
The sensor may be internal (contained in a room or on a surface in a room) or external. An external sensor would be the equivalent of a weather compensated system or outdoor temperature reset. Several radiators may use the same internal sensor—e.g., all rooms on the west façade of a building may be controlled by a single sensor. As would be appropriate for a hydronic loop in a conditioned slab, one surface temperature sensor per zone is available for use with on/off or proportional controls. The surface vs. zone location of the sensor is determined by selection of the sensed variable and tagging of the sensed surface within the Apache Thermal view. For more information on using surface temperature sensors, see section 6.3.2 Sensed variables.
Select an appropriate sensor location. This must be done separately for both Proportional Flow and Temperature controllers when they are included.
Sensed variable
Select the variable that is to be used in the proportional control. This must be done separately for both Proportional Flow and Temperature controllers when they are included.
Surface temperature is available as a sensed variable for use with on/off or proportional controls, as would be appropriate for a hydronic loop in a conditioned slab. The surface vs. zone location of the sensor is determined by selection of the sensed variable.  The specific surface adjacency for the sensor location must also be tagged within the Apache Thermal view. For more information on using surface temperature sensors, see section 6.3.2 Sensed variables.
Note: While Flow rate is on the Room Unit controller selection list of Sensed variables and does cause gpm or l/s units to be displayed, this sensed variable is not yet available for Room Unit controllers.
Midband variation
The midband for proportional control may be constant or variable—i.e., timed, scheduled, or determined by a formula profile (see section 6.6.4.2 ). Select Constant or Timed as appropriate.
This must be completed for Proportional Flow and Temperature controllers when they are used.
Midband or variation profile
Enter a fixed midband value if Constant or select an appropriate midband variation profile if the variation is timed (see section 6.6.4.3 ).
This must be completed for Proportional Flow and Temperature controllers when they are used.
Proportional bandwidth
The proportional bandwidth is the width of the band used for proportional control—i.e., the range of the sensed variable over which the proportional control will vary as bounded by maximum and minimum sensed values. This proportional bandwidth is centered about the midband (see section 6.6.4.4 ). Enter the bandwidth as appropriate.
This must be completed for Proportional Flow and Temperature controllers when they are used.
Maximum change per time step
This parameter specifies the maximum fractional change that the controller can carry out in each simulation time step. The fraction is with respect to the overall range of control between the value at Max signal and the value at Min signal (see section 6.6.4.5 ).
Enter a value as needed to maintain stable operation of the unit. This must be complete for Proportional Flow and Temperature controllers when they are used. A good starting point is 0.2 to 0.3. If operation is unstable, reduce this value as needed—e.g., to 0.1 or 0.05.
Flow at Minimum Control Signal
When proportional Flow control is used, enter the water flow rate that corresponds to the minimum signal from the proportional controller. If no proportional Flow controller is specified, the value entered here will be ignored. The minimum control signal is generated when the sensed value is at or below the midband minus half the proportional band.
Temperature at Minimum Control Signal
When proportional Temperature control is used, enter the water temperature that corresponds to the minimum signal from the proportional controller. If no proportional controller was specified, the value entered here will be ignored. Note that the minimum control signal is generated when the sensed value is at or below the midband minus half the proportional band.
Radiant fraction (for sensor)
When the sensed variable is dry-bulb temperature, an input field is available to set the radiant fraction of temperature sensor. As an example, if the radiant fraction were set to 0.5, the sensor would effectively be sensing dry resultant temperature—i.e., operative temperature in still air conditions. 
Enter an appropriate value for a radiant fraction.
Orientation
When the sensed variable is Solar radiation, enter the orientation or azimuth of sensing surface in degrees (0 deg = North and 180 deg = South)
Slope
When the sensed variable is Solar radiation, enter the slope (angle from horizontal) of the surface containing the sensor in degrees (0 deg = horizontal and 90 deg = vertical)
AND References
Add/Remove logical AND connections to other controllers as appropriate (see section 6.6.5 ).
OR Reference
Add/Remove logical OR connections to other controllers as appropriate (see section 6.6.6 ).