4.16.2 Results

         The results variables that can be calculated for Power station are defined below:
·        ​ Air volume flow rate: The volume flow rate of air through the cooling tower
·        Approach: The temperature difference between the air wet-bulb temperature and the cold water temperature.
·        Auxiliary power consumption: ​Fraction of total electricity generated by the steam turbine that is used to power auxiliary equipment at the power plant (i.e. parasitic power).
·        ​Blowdown water: Water added to the cooling tower system to counteract fouling (prevent a build-up of impurities on cooling tower equipment).​
·        Cooling waste heat generation: Heat yielded from fuel that requires cooling by the cooling system.
·        COP: The coefficient of performance for the cooling tower.  It's the heat rejection rate divided by the electricity consumption.
·        Direct CO2 emission: ​CO2 emitted by this installation from combustion
·        Electricity consumption: The total electricity consumed (pump+fan)
·        ​Entering air dry-bulb temperature: The dry-bulb temperature of the entering (ambient) air.
·        ​Entering air enthalpy: The enthalpy of the entering (ambient) air.
·        ​Entering air humidity: The proportion of water vapour in the entering (ambient) air (in kg of water per kg or air)
·        ​Entering air wet-bulb temperature: The wet-bulb temperature of the entering (ambient) air.
·        ​Entering water temperature: The temperature of water entering the cooling tower.  This is always greater than or equal to the leaving water temperature.
·        ​Fan power consumption: The electricity consumed to operate the fan.​
·        Flue gas heat losses: ​Heat lost from the power plant via the flue gas exhaust pipe or other direct heat loss mechanisms.  This loss is proportional to the fuel consumption.
·        Fuel consumption: ​Fuel consumed by the power station (given in terms of energy released on combustion)
·        Grid electricity generation: Electricity generated by the power station which heads over to the grid (before line losses).
·        Leaving air dry-bulb temperature: ​​The dry-bulb temperature of the air leaving the cooling tower.
·        Leaving air enthalpy: The enthalpy of the air leaving the cooling tower.
·        Leaving air humidity: The proportion of water vapour in the air leaving the cooling tower (in kg of water per kg or air)
·        Leaving air wet-bulb temperature: The wet-bulb temperature of the air leaving the cooling tower.
·        ​Leaving water temperature: ​The temperature of water leaving the cooling tower.  This is always less than or equal to the entering water temperature.
·        ​Overload flag: True (or 1) if the cooling tower is overloaded, false​ (or 0) otherwise.
·        Plant efficiency: Efficiency of the power station
·        ​Pump power consumption: The electricity consumed to operate the pump.​
·        ​Range: The temperature difference between the warm water temperature and the cold water temperature.
·        Total electricity generation: Electricity generated by the power station
·        Waste heat processed: Waste heat processed on-site by the power plant's cooling system.
·        ​Waste heat rejected: The amount of waste heat removed from the circulating fluid and rejected to the environment.
·        ​Water consumption: Water consumed by the cooling tower (this is the fresh water supply water that replaces blow-down, windage drift and evaporation losses).
·        ​Water volume flow rate: ​The circulating water flow rate
·        ​Water withdrawal: Water withdrawn from the potable water supply.  For a cooling tower cooling system, this is the same as the water consumption.
·        ​Windage drift losses: Water lost from the cooling tower system due to windage drift (droplets propelled out of the cooling tower by the fan.